SE3000 Series Field Data Scanning Units

SE3000 series scanning units are designed for data logging with a personal computer. The basic unit with 6 input points can be connected to 7 sub units (6 input points / sub unit) and maximum 48 analog data can be collected. Two soft ware packages, "KIDS" for data logging and "PASS" for parameter programming, are available.


Expanded type units can expand input points up to 48 points by connecting sub units (6-point input).

Data can be easily collected by the data logging software package "KIDS" and the parameter programming software package "PASS". The "KIDS" can connect up to 5 sets of SE3000 and manage up to 100 channels.

3 kinds of communications interfaces of RS-232C, RS-422A and are built-in.

The communications protocol is MODBUS for easy system configuration.

Universal input (32 kinds of DC voltage, thermocouples and resistance thermometers)

Input is isolated between all channels.

The unit can be used with BR series graphic recorder as an input extension unit (up to 24 points).
CE conformance

Measuring points: 12, 24 and 36 points

Input: Multi-channel data range
DC voltage --- ±10mV, ±20mV, ±40mV, ±80mV, ±1.25V, ±2.5 V, ±5 V, ±10V DC current --- Shunt resistor
(100Ω, 250Ω) needs to be mounted externally Thermocouple --- B, R, S, K, E, J, T, N, PtRh40-PtRh20,
NiMo-Ni,WRe5 – WRe26, W-WRe26, Platinel II, U, L
Resistance thermometer --- Pt 100, JPt 100

Range setting:
Input type and range are set with front keys

Scale setting:
The minimum and maximum values and unit are set for each point with front keys Setting range -30000 to 30000
Decimal points Optional setting

Indication accuracy:
Refer to items of measuring ranges, accuracy rating and display resolutions

Temperature drift:
0.1% FS/ 10°C

Measuring period:
0.1 sec/ channel

Reference junction compensation accuracy:
K, E, J, T, N, Platinel II --- ±0.5°C or less (0℃°C or more when measuring) R, S, WRe5-WRe26, NiMo-Ni, U, L --- ±1.0°C or less (Only when the ambient temperature is 23°C±5°C)

Input resolution:
Approx. 1/40000 (Standard range conversion)

Burnout:
Select with/ without burnout for each input

Allowable signal source resistance:
Thermocouple inputs, DC voltage input (10mV) --- 500Ω or less (without burnout) DC Voltage input (except 10mV) --- 100Ω or less Resistance thermometer inputs --- 10Ω or less/ line Three lines are common, Pt100, JPt100

Input resistance:
Thermocouple input, DC voltage input --- approx.1MΩ

Maximum input applied voltage:
±20V DC palm concepcion

Input correction:
Zero/span correction and shift correction for each channel

Maximum common mode voltage:
30V AC (support LVD) *250V AC at evaluation

Common mode rejection ratio:
130dB

Series mode rejection ratio:
50dB (Only when the peak value of noise is below standard range.)

Terminal board:
Detachable type, removable for wire connection